Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) 2 GROUND RODS REQUIRED 6' MINIMUM APART 2) BOND GAS PIPING, WATER, TO NEW SERVICE 3) MARKING PEN NOT APPROVED AS ADDRESS LABEL ON SERVICE, MUST BE A PERMANENT LABEL SCREWED OR RIVITED TO ENCLOSURE |