Permit: T05EL01482

Parcel: 138080110

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/26/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) 2 GROUND RODS REQUIRED 6' MINIMUM APART
2) BOND GAS PIPING, WATER, TO NEW SERVICE
3) MARKING PEN NOT APPROVED AS ADDRESS LABEL ON SERVICE, MUST BE A PERMANENT LABEL SCREWED OR RIVITED TO ENCLOSURE