Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
MULTI FAMILY OTHER
Apply Date:
04/19/2005
Applicant:
JUSTIN BUNGER
Description:
ELEC UPGRADE TO 200AMP

Permit Reviews

Permit Number - T05EL00793
Permit Status: Expired
Permit Description: ELEC UPGRADE TO 200AMP
Start Date Submittal Complete Date Status  
04/19/2005 OTHER 04/19/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05EL00793
Permit Status: Expired
Permit Description: ELEC UPGRADE TO 200AMP
Total Outstanding Activity Conditions - 1
Date Name
04/19/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05EL00793
Permite Description: ELEC UPGRADE TO 200AMP
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
ELECTRIC - SERVICE UPGRADE N/A Not Inspected
05/31/2005 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) THIS IS A DUPLEX-IS THIS UNDER ONE METER AND SINGLE MANAGEMENT?. 2) PLEASE ADDRESS ACCORDINGLY. 3) LABEL BREAKERS AS TO CIRCUITS & UNITS. 4) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURERS REQUIREMENTS. 5) PROPERLY INSTALL AND SUPPORT CONDUIT BELOW PANEL ALSO PVC TO BE LISTED FOR ELECTRICAL. 6) PLEASE VERIFY GAS & WATER BONDING. 7) FILL UNUSED PORTION OF HOLE IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT.