Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THIS IS A DUPLEX-IS THIS UNDER ONE METER AND SINGLE MANAGEMENT?. 2) PLEASE ADDRESS ACCORDINGLY. 3) LABEL BREAKERS AS TO CIRCUITS & UNITS. 4) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURERS REQUIREMENTS. 5) PROPERLY INSTALL AND SUPPORT CONDUIT BELOW PANEL ALSO PVC TO BE LISTED FOR ELECTRICAL. 6) PLEASE VERIFY GAS & WATER BONDING. 7) FILL UNUSED PORTION OF HOLE IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT. |