Permit: T05EL00793

Parcel: 11007380A

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/31/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) THIS IS A DUPLEX-IS THIS UNDER ONE METER AND SINGLE MANAGEMENT?. 2) PLEASE ADDRESS ACCORDINGLY. 3) LABEL BREAKERS AS TO CIRCUITS & UNITS. 4) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURERS REQUIREMENTS. 5) PROPERLY INSTALL AND SUPPORT CONDUIT BELOW PANEL ALSO PVC TO BE LISTED FOR ELECTRICAL. 6) PLEASE VERIFY GAS & WATER BONDING. 7) FILL UNUSED PORTION OF HOLE IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT.