Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP

Permit Reviews

Permit Number - T05EL00165
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Start Date Submittal Complete Date Status  
01/25/2005 ELECTRICAL 01/26/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05EL00165
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Activity Conditions - 1
Date Name
01/25/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05EL00165
Permite Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
01/28/2005 ELECTRIC - UNDERGROUND N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/28/2005 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999* 1. 1 1/2"LB ON SIDE OF SERVICE MUST HAVE A CLOSED NIPPLE WITH LOCKNUTS-ONE ON INSIDE ONE ON OUTSIDE. 2) 1ST GROUND RED BELOW SERVICE, ONLY ONE #4 GROUND CAN PASS THUR IT AND IT MUST PASS THUR HOLE WITH BOLT NOT THUR CLAMP. 3) 2ND GROUND REO-ACORN/ CLAMP CAN HAVE ONLY ONE #4 THUR IT, NOT RATED FOR TWO . 4) INSTALL DEAD FRONT COVER . RECALL FOR INSPECTION.
02/02/2005 ELECTRIC - SERVICE UPGRADE N/A Partial Approval IVRS - Inspection :*
1) NOTES: STRAP #4 ABOVE PANEL TO WALL
2) RECALL FOR FINAL AFTER TIE-IN

Completed Inspections

Permit Status: Expired
Permit Number: T05EL00165
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Completed Inspections - 1
Date Description Inspector Results Comments
02/03/2005 TEP CLEARANCE - AM SLONG Approved OK TO CLEAR INCREASE