Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL00165
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 1 1/2"LB ON SIDE OF SERVICE MUST HAVE A CLOSED NIPPLE WITH LOCKNUTS-ONE ON INSIDE ONE ON OUTSIDE. 2) 1ST GROUND RED BELOW SERVICE, ONLY ONE #4 GROUND CAN PASS THUR IT AND IT MUST PASS THUR HOLE WITH BOLT NOT THUR CLAMP. 3) 2ND GROUND REO-ACORN/ CLAMP CAN HAVE ONLY ONE #4 THUR IT, NOT RATED FOR TWO . 4) INSTALL DEAD FRONT COVER . RECALL FOR INSPECTION. |