Permit: T05CM05166
Permit Details
Status:
C of o
Type:
COMMERCIAL OTHER
Address:
5170 E GLENN ST #170
Address NEW:
5170 E GLENN ST #170
Apply Date:
10/12/2005
Applicant:
CAMWEST GROUP INC
Description:
TI: DENTAL
Contractors:
- CAMWEST GROUP INC
Permit Reviews
Permit Number - T05CM05166
Permit Status: C of o
Permit Description: TI: DENTAL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/12/2005 | PLANS OK TO SUBMIT - COMM | 10/12/2005 | COMPLETED |
| 10/12/2005 | 3RD PARTY REVIEW-COMMERCIAL TI | 11/10/2005 | COMPLETED |
| 12/14/2005 | 3RD PARTY REVIEW-REVISION/OTHER | 12/15/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM05166
Permit Status: C of o
Permit Description: TI: DENTAL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/12/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T05CM05166
Permit Description: TI: DENTAL
Total Completed Inspections - 24
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2005 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | IVRS - Inspection :*SOIL WATER TEST IS OK P.O.C OF NEW BLDG. DRAINS TO EXSISTING BLDG. DRAINS ARE OK OK TO BACKFILL THE TRENCH. |
| 12/14/2005 | MEDICAL - GAS/TEST INTERMED | RMYERS | Approved | IVRS - Inspection :* 1. PRE-CON: CAMWEST, LMHANNA CO., STEVE GIBBONS 2. UNDERGROUND VACUUM SCH 40 PVC OK 1/2" TYPE "L" AIRLINES UNDERSLAB OK CONTRACTOR TO REDLINE CHANGES OK TO COVER -- DON'T FORGET TO CALL AT TIME OF STAGING. |
| 12/15/2005 | FRAMING | JCAGLE | Approved | IVRS - Inspection :* 1) OBSERVED PRE-SLAB INFILL/POUR BACKS FOR PLUMBING AND ELECTRIC LINES 2) CONTRACTOR IN PROGRESS OF ADDING BLDG PRE-SLAB (01015) WILL CALL WHEN ADDED |
| 12/15/2005 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection :* |
| 01/11/2006 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :*OK WALLS AND HARD CEILINGS |
| 01/17/2006 | BUILDING PRE-SLAB | JCAGLE | Approved | IVRS - Inspection :* |
| 01/24/2006 | PLUMBING - INTERMEDIATE | TRINIVJR | Approved | IVRS - Inspection :*DWV WATER TEST IS OK OVERHEAD WATER DISTRIBUTION IS OK OK FOR DRYWALL |
| 02/10/2006 | SHEET ROCK NAILING | JCAGLE | Approved | IVRS - Inspection :* FIRE CAULKING COMPLETE |
| 02/10/2006 | ELECTRIC - ABOVE CEILING | RMAJUTA | Approved | IVRS - Inspection :* 1. VERIFIED BOND TO OXYGEN, NITRO OXIDE, MEDICAL AIR OK TO CLEAR ECO |
| 02/10/2006 | TEP CLEARANCE - PM | JWEATHER | Approved | OK TO CLEAR #170 FOR ECO PER R. MAJUTA |
| 02/10/2006 | ELECTRIC - TEMP POWER FOR TEST | RMAJUTA | Approved | IVRS - Inspection :* |
| 02/13/2006 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | IVRS - Inspection :* |
| 03/01/2006 | ENGINEERING - FINAL | JBRUCKME | Approved | |
| 03/01/2006 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 03/01/2006 | FIRE - FINAL | LTHOMAS | Approved | |
| 03/01/2006 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 03/01/2006 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | PER EMAIL |
| 03/02/2006 | ELECTRIC - PROGRESS | RHOLLAND | Approved | IVRS - Inspection :* |
| 03/03/2006 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection :* EXT RINGS, EXT CORD OUT LETTER CHAIRS NOT USED |
| 03/03/2006 | MEDICAL GAS - FINAL | RMYERS | Approved | MECHICAL GAS FINAL OK |
| 03/03/2006 | PLUMBING - MEDICAL GAS/FINAL | RMYERS | Approved | MECHICAL GAS FINAL OK |
| 03/03/2006 | PLUMBING - FINAL | RMYERS | Approved | NOT ALL CHAIRS ARE INSTALLED:THE CHAIRS THAT ARE INSTALLED, ARE INSTALLED CORRECTLY.OK FOR C OF O PENDING ANY OTHER INSPECTION. |
| 04/26/2006 | MECHANICAL - FINAL | JMILITEL | Approved | OK FOR FINAL C OF O |
| 04/27/2006 | BUILDING - FINAL | JMILITEL | Approved | OK FOR FINAL C OF O |