Permit: T05CM05166

Parcel: 110121170

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/11/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*OK WALLS AND HARD CEILINGS
01/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BRANCH CIRCUIT TO BE AS PER 517.13
2. PROTECT M/C CABLE IN CHANNEL AS PER 300.4
3. DO NOT BUNDLE M/C CABLES
4. SECURE M/C WITHIN 12" OF CANS