Permit: T05CM04957
Permit Details
Apply Date:
09/28/2005
Applicant:
METRO PERMIT EXPRESS, INC *C
Description:
TI: OFFICE
Architects:
- COLE, BENJAMIN WILLIAM
Permit Reviews
Permit Number - T05CM04957
Permit Status: C of o
Permit Description: TI: OFFICE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
09/28/2005 | COMMERCIAL TI | 10/10/2005 | COMPLETED |
10/10/2005 | RESUBMITTAL | 10/13/2005 | COMPLETED |
10/21/2005 | REVISION | 10/21/2005 | COMPLETED |
11/01/2005 | REVISION - WALK THRU | 11/01/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM04957
Permit Status: C of o
Permit Description: TI: OFFICE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/28/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T05CM04957
Permit Description: TI: OFFICE
Total Completed Inspections - 16
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2005 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | IVRS - Inspection :*DELETED PLBG. FIXTURES HAVE BEEN REMOVED & PERM CAP UNDER FLOOR OK TO BACKFILL TRENCH |
11/16/2005 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
11/16/2005 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :*INSULATE CONDENSATE DRIAN LINE AS PER PLAN ?? WILL CHECK ON FINAL. OK FOR CEILING TILES |
11/16/2005 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :*ABOVE CEILING: SUPPORT M/C CABLES AS PER 300.11 AND AT EXIT OF WALL ALSO WITHIN 12" OF BOX SUPPORT WIRE NEEDED FOR EXIT LIGHTING ALL FIXTURES TO BE SECURELY ATTACHED TO GRID PLEASE REMOVE OLD VDV CABLEING OR MARK AS PER 800.2 ALSO FINISH SUPPORTING AS PER 725.6 ( T-STAT) |
11/17/2005 | FIRE - FINAL | LTHOMAS | Approved | |
11/21/2005 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :*OK FOR FINAL C OF O |
11/21/2005 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :*OK FINAL |
11/21/2005 | ELECTRIC - ABOVE CEILING | RHOLLAND | Approved | IVRS - Inspection :* |
11/22/2005 | PLUMBING - FINAL | TRINIVJR | Approved | IVRS - Inspection :*PLBG FINAL IS OK OK FOR C OF O |
11/22/2005 | ENGINEERING - FINAL | JBRUCKME | Approved | |
11/22/2005 | BUILDING - FINAL | JCAGLE | Approved | IVRS - Inspection :*APPROVED |
11/22/2005 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
11/22/2005 | SHEET ROCK NAILING | JCAGLE | Approved | IVRS - Inspection :*FIRE SEPARATION INSTALLATION FINISHED AT NORTH DEMISING WALL |
11/22/2005 | PLUMBING - PROGRESS | TRINIVJR | Approved | IVRS - Inspection :* |
11/22/2005 | PLUMBING - INTERMEDIATE | TRINIVJR | Approved | IVRS - Inspection :* |
11/29/2005 | PERMIT FINALED | LJACKSON | Approved |