Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Apply Date:
09/28/2005
Applicant:
METRO PERMIT EXPRESS, INC *C
Description:
TI: OFFICE
Architects:
  • COLE, BENJAMIN WILLIAM

Permit Reviews

Permit Number - T05CM04957
Permit Status: C of o
Permit Description: TI: OFFICE
Start Date Submittal Complete Date Status  
09/28/2005 COMMERCIAL TI 10/10/2005 COMPLETED Review Details
10/10/2005 RESUBMITTAL 10/13/2005 COMPLETED Review Details
10/21/2005 REVISION 10/21/2005 COMPLETED Review Details
11/01/2005 REVISION - WALK THRU 11/01/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM04957
Permit Status: C of o
Permit Description: TI: OFFICE
Total Outstanding Activity Conditions - 1
Date Name
09/28/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM04957
Permit Description: TI: OFFICE
Total Completed Inspections - 16
Date Description Inspector Results Comments
11/03/2005 PLUMBING - ROUGH, SOIL TRINIVJR Approved IVRS - Inspection :*DELETED PLBG. FIXTURES HAVE BEEN REMOVED & PERM CAP UNDER FLOOR
OK TO BACKFILL TRENCH
11/16/2005 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
11/16/2005 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*INSULATE CONDENSATE DRIAN LINE AS PER PLAN ?? WILL CHECK ON FINAL. OK FOR CEILING TILES
11/16/2005 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*ABOVE CEILING:
SUPPORT M/C CABLES AS PER 300.11 AND AT EXIT OF WALL ALSO WITHIN 12" OF BOX
SUPPORT WIRE NEEDED FOR EXIT LIGHTING
ALL FIXTURES TO BE SECURELY ATTACHED TO GRID
PLEASE REMOVE OLD VDV CABLEING OR MARK AS PER 800.2
ALSO FINISH SUPPORTING AS PER 725.6 ( T-STAT)
11/17/2005 FIRE - FINAL LTHOMAS Approved
11/21/2005 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*OK FOR FINAL C OF O
11/21/2005 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*OK FINAL
11/21/2005 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
11/22/2005 PLUMBING - FINAL TRINIVJR Approved IVRS - Inspection :*PLBG FINAL IS OK
OK FOR C OF O
11/22/2005 ENGINEERING - FINAL JBRUCKME Approved
11/22/2005 BUILDING - FINAL JCAGLE Approved IVRS - Inspection :*APPROVED
11/22/2005 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
11/22/2005 SHEET ROCK NAILING JCAGLE Approved IVRS - Inspection :*FIRE SEPARATION INSTALLATION FINISHED AT NORTH DEMISING WALL
11/22/2005 PLUMBING - PROGRESS TRINIVJR Approved IVRS - Inspection :*
11/22/2005 PLUMBING - INTERMEDIATE TRINIVJR Approved IVRS - Inspection :*
11/29/2005 PERMIT FINALED LJACKSON Approved