Permit: T05CM03991
Permit Details
Apply Date:
07/29/2005
Applicant:
TUCSON ELECTRIC
Description:
MODEL: PHOTOVOLTAIC SYSTEM TD#16-33-60
Permit Reviews
Permit Number - T05CM03991
Permit Status: Final
Permit Description: MODEL: PHOTOVOLTAIC SYSTEM TD#16-33-60
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/29/2005 | OTHER | 08/11/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM03991
Permit Status: Final
Permit Description: MODEL: PHOTOVOLTAIC SYSTEM TD#16-33-60
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/29/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05CM03991
Permit Description: MODEL: PHOTOVOLTAIC SYSTEM TD#16-33-60
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2005 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN LOOSE SEAL TITE/CAR FLEX FITTINGS 2) PROVIDE PV LABELING AS PER 690.17 3) DC DISCONNECTING MEANS NOT LABELED FOR DC 4) CLEAN SURFACE UNDER LUG 250.12 5) SUPPORT CONDUIT TO ROOF AS PER CODE 6) SUPPORT JUNCTION BOX ON ROOF 7) TIGHTEN STRAIN RELIEF CONNECTORS AND CONNECTORS TO BE SIZED CORRECTLY FOR CABLES 8) SUPPORT PV CONDUCTOR CABLES/OFF OF ROOF 9) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 10) WIRING METHODS NOT PER PLANS 11) PV CONDUCTOR NOT SIZED PER PLANS. ALSO EQUIPMENT GROUND CONDUCTOR NOT SIZED AS PER PLANS |
| 09/15/2005 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 09/16/2005 | BUILDING - FINAL | AMATHIES | Approved | IVRS - Inspection :* |
| 09/16/2005 | FRAMING | AMATHIES | Approved | IVRS - Inspection :* |
| 02/14/2006 | TEP CLEARANCE - AM | JKOZUCH | Approved | ECO PV SYSTEM |
| 02/14/2006 | PERMIT FINALED | JKOZUCH | Approved |