Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05CM03991

Parcel: 127033310


Addresses:

5525 E 3RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/13/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/23/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/13/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/04/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. DC LABELING TO BE FROM MANUFACTURER PER LISTING LABEL.
2. GROUNDING CONNECTIONS AT ARRAYS LOOSE
3. SUPPORT NON METALLIC FLEX UP OFF OF ROOF
4. WHITE CONDUCTOR NOT TO BE TAPED FOR A HOT CONDUCTOR
5. FINISH PREVIOUS ITEMS #1,3,4,5,7 AND 10
09/15/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE SEAL TITE/CAR FLEX FITTINGS
2) PROVIDE PV LABELING AS PER 690.17
3) DC DISCONNECTING MEANS NOT LABELED FOR DC
4) CLEAN SURFACE UNDER LUG 250.12
5) SUPPORT CONDUIT TO ROOF AS PER CODE
6) SUPPORT JUNCTION BOX ON ROOF
7) TIGHTEN STRAIN RELIEF CONNECTORS AND CONNECTORS TO BE SIZED CORRECTLY FOR CABLES
8) SUPPORT PV CONDUCTOR CABLES/OFF OF ROOF
9) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8
10) WIRING METHODS NOT PER PLANS
11) PV CONDUCTOR NOT SIZED PER PLANS. ALSO EQUIPMENT GROUND CONDUCTOR NOT SIZED AS PER PLANS