Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/23/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/13/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/04/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. DC LABELING TO BE FROM MANUFACTURER PER LISTING LABEL. 2. GROUNDING CONNECTIONS AT ARRAYS LOOSE 3. SUPPORT NON METALLIC FLEX UP OFF OF ROOF 4. WHITE CONDUCTOR NOT TO BE TAPED FOR A HOT CONDUCTOR 5. FINISH PREVIOUS ITEMS #1,3,4,5,7 AND 10 |
|
| 09/15/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN LOOSE SEAL TITE/CAR FLEX FITTINGS 2) PROVIDE PV LABELING AS PER 690.17 3) DC DISCONNECTING MEANS NOT LABELED FOR DC 4) CLEAN SURFACE UNDER LUG 250.12 5) SUPPORT CONDUIT TO ROOF AS PER CODE 6) SUPPORT JUNCTION BOX ON ROOF 7) TIGHTEN STRAIN RELIEF CONNECTORS AND CONNECTORS TO BE SIZED CORRECTLY FOR CABLES 8) SUPPORT PV CONDUCTOR CABLES/OFF OF ROOF 9) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 10) WIRING METHODS NOT PER PLANS 11) PV CONDUCTOR NOT SIZED PER PLANS. ALSO EQUIPMENT GROUND CONDUCTOR NOT SIZED AS PER PLANS |