Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Apply Date:
07/05/2005
Applicant:
SWAN WAYNE E
Description:
TI:OFFICE
Contractors:
  • J W S CONSTRUCTION INC ,

Permit Reviews

Permit Number - T05CM03304
Permit Status: C of o
Permit Description: TI:OFFICE
Start Date Submittal Complete Date Status  
07/05/2005 COMMERCIAL TI 07/25/2005 COMPLETED Review Details
09/12/2005 REVISION 09/28/2005 COMPLETED Review Details
10/25/2005 REVISION 10/26/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM03304
Permit Status: C of o
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date Name
07/05/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM03304
Permit Description: TI:OFFICE
Total Completed Inspections - 19
Date Description Inspector Results Comments
09/30/2005 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :* OK FOR CEILING TILES. NEW BATHROOMS WIL BE PHASE 2.
11/09/2005 PLUMBING - ROUGH, SOIL TRINIVJR Approved IVRS - Inspection :*DWV WATER TEST IS OK
P.O.C OF NEW BLDG DRAIN TO EXISTING BLDG. DRAIN IS OK
OK TO BACKFILL THE TRENCH.
11/09/2005 PLUMBING - PROGRESS TRINIVJR Approved IVRS - Inspection :*
11/10/2005 FIRE - FINAL LTHOMAS Approved
11/12/2005 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
1. PLEASE CLOSE BOX WITH EXPOSED CONDUCTORS & FILL UNUSED OPENINGS.
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING (314.20)
3. M/C CABLES ABOVE CEILING NOT SUPPORTED AT ALL
4. USE APPROVED FITTINGS FOR OFFICE FURNITURE CONNECTIONS - TIGHTEN LOOSE FITTINGS
5. NOTE 3 CALLS FOR NEW EXIT LIGHTS
6. AREAS OCCUPIED WITHOUT INSPECTIONS.
11/12/2005 PLUMBING - INTERMEDIATE TRINIVJR Approved IVRS - Inspection :*OVERHEAD WATER DISTRIBUTION IS OK
11/12/2005 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
11/14/2005 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :* PHASE I COMPLETE, MECHANICALLY OK TO OCCUPY
11/14/2005 BUILDING - FINAL JCAGLE Approved IVRS - Inspection :*
11/22/2005 ELECTRIC - INTERMEDIATE RSUBA Approved IVRS - Inspection :*OK WALLS BATHROOMS ( 3) OFFICE # 131 B
11/22/2005 FRAMING JCAGLE Approved IVRS - Inspection :*RESTROOMS, STORAGE 146 B, OFFICE 131 B,NEW WALL @ HALLWAY 103
12/02/2005 SHEET ROCK NAILING JCAGLE Approved IVRS - Inspection :*RESTROOMS, STORAGE 146 B, OFFICE 131 B, NEW WALL @ HALLWAY 103
01/08/2006 PLUMBING - ABOVE CEILING TRINIVJR Approved IVRS - Inspection :*
1. ABOVE CEILING IS OK
01/12/2006 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
01/12/2006 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
01/13/2006 ENGINEERING - FINAL JBRUCKME Approved
01/20/2006 RIGHT OF WAY - FINAL PWHIDDON Approved PER EMAIL
02/08/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved
02/08/2006 PERMIT FINALED DROBEY Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CERT OF OCC VIEW