Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM03304
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/12/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CLEAN EXCESS PAINT FROM DEVICE TERMINALS 2) FINISH ITEMS #2 AND 4 OF PREVIOUS INSPECTION |
|
11/12/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE CLOSE BOX WITH EXPOSED CONDUCTORS & FILL UNUSED OPENINGS. 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING (314.20) 3. M/C CABLES ABOVE CEILING NOT SUPPORTED AT ALL 4. USE APPROVED FITTINGS FOR OFFICE FURNITURE CONNECTIONS - TIGHTEN LOOSE FITTINGS 5. NOTE 3 CALLS FOR NEW EXIT LIGHTS 6. AREAS OCCUPIED WITHOUT INSPECTIONS. |