Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03304

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/12/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CLEAN EXCESS PAINT FROM DEVICE TERMINALS
2) FINISH ITEMS #2 AND 4 OF PREVIOUS INSPECTION
11/12/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLEASE CLOSE BOX WITH EXPOSED CONDUCTORS & FILL UNUSED OPENINGS.
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING (314.20)
3. M/C CABLES ABOVE CEILING NOT SUPPORTED AT ALL
4. USE APPROVED FITTINGS FOR OFFICE FURNITURE CONNECTIONS - TIGHTEN LOOSE FITTINGS
5. NOTE 3 CALLS FOR NEW EXIT LIGHTS
6. AREAS OCCUPIED WITHOUT INSPECTIONS.