Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T05CM01508
Permit Details
Apply Date:
04/06/2005
Applicant:
N/A
Description:
ADDITION:DIESEL FUEL STATION
Contractors:
- ENVIRONMENTAL STRATEGIES INC ,
Permit Reviews
Permit Number - T05CM01508
Permit Status: Expired
Permit Description: ADDITION:DIESEL FUEL STATION
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
04/06/2005 | COMMERCIAL NEW | 04/21/2005 | COMPLETED |
04/21/2005 | COMMERCIAL NEW | 04/27/2005 | COMPLETED |
04/27/2005 | 3RD PARTY REVIEW-COMMERCIAL TI | 05/03/2005 | COMPLETED |
05/03/2005 | POST 3RD PARTY REVIEW | 05/10/2005 | COMPLETED |
07/25/2005 | REVISION | 07/25/2005 | COMPLETED |
08/31/2005 | REVISION - WALK THRU | 08/31/2005 | COMPLETED |
10/05/2005 | 3RD PARTY REVIEW-REVISION/OTHER | 10/11/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM01508
Permit Status: Expired
Permit Description: ADDITION:DIESEL FUEL STATION
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
04/06/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T05CM01508
Permite Description: ADDITION:DIESEL FUEL STATION
Total Outstanding Inspections - 7
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
BUILDING PRE-SLAB | N/A | Not Inspected | ||
BUILDING - FINAL | N/A | Not Inspected | ||
PLUMBING - FINAL | N/A | Not Inspected | ||
FIRE - FINAL | N/A | Not Inspected | ||
08/31/2005 | PLUMBING - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection :* 1) PROVIDE ITEMS #4 AND #5 FROM 8/30/05 |
08/31/2005 | PLUMBING - GAS PRESS TEST FNL | N/A | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO VIEW TEST FROM 2" I.P. BALL VALVES THRE SHEAR VALVE TO METER |
09/06/2005 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* |
Completed Inspections
Permit Status: Expired
Permit Number: T05CM01508
Permit Description: ADDITION:DIESEL FUEL STATION
Total Completed Inspections - 7
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2005 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | IVRS - Inspection :* 1) THERE IS NO ROUGH PLBG INSTALLED OR REQUIRED ON THIS ACTIVITY. |
06/28/2005 | EXCAVATION/LAYOUT REBAR & ZON | AMATHIES | Approved | IVRS - Inspection :* |
08/31/2005 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :* 1) 100 PSI TEST FROM TANKS AT INLET TO CHECK VALVE TO 2" I.P. BALL VALVES AT DISCHARGE OF FILTER OK |
09/01/2005 | ELECTRIC - RECONNECT | DSANTACR | Approved | IVRS - Inspection :* |
09/01/2005 | ELECTRIC - SERVICE UPGRADE | DSANTACR | Approved | IVRS - Inspection :* |
09/01/2005 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
09/02/2005 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :* 1) FILL ? WITH ? OK-PM RETURN INSPECTION 2) VERIFY BY ENGINEER THAT CONTROL CABINET AND WIRING IN COMPLIANCE WITH 514.11 AND 514.13 NEC IT APPEARS THAT THERE ARE NO PROVISIONS FOR NEUTRAL DISCONNECTING 3) INSTALL LEVEL PROBES |