Permit: T05CM01508

Parcel: 13216600B


Addresses:

4220 S PARK AV


Inspection Status: Partial Approval

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM01508

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
08/31/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE ITEMS #4 AND #5 FROM 8/30/05
08/30/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROVIDE ADDITIONAL SUPPORTS FOR PIPING AT CHANGES OF DIRECTION AND APPROPRIATE DISTANCES FOR PIPE SIZE
2) PROVIDE 3" RELIEF AND PIPING PER APPROVED PLAN OR HAVE PLAN REVISED AND CITY APPROVED
3) PROVIDE SPEC. BOOK FOR VALVING ON THIS 50B. WE ARE SEIING 300# FLANGED VALVES BEING INTERMINGLED WITH 150# THREADED VALVES
4) PROVIDE MODEL 52A PRESSURE REGULATOR VALVE WITH SHEAR SECTION PER PLAN
5) PROVIDE ON SITE TEST OF SECONDARY CONTAINMENT OF TANKS. WHAT IS PRESSURE. PLEASE PROVIDE SPEC. BOOK
6) 100 PSI TEST SHALL HOLD PRESSURE
7) PROVIDE 3" VENT PRIMARY AND SECONDARY PER PLAN
8) FINISH BOLT UP OF LADDERS, RAILING, ETC...
07/26/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) REVISED CITY APPROVED PLAN ON SITE
2) THIS INSPECTION CNG SYSTEM ONLY 5000 PSI TEST ON 3/4" SUPPLY TUBING FROM MAIN SUPPLY CABINET OVERHEAD TO (2) PUMP STATIONS OK
2) 50 PSI TEST ON VENT 1/2" TUBING FROM ? LOCATION TO (2) PUMP STATIONS OK
3) CONTRACTOR TO MAKE FINAL CONNECTIONS TO COMPLETE SYSTEM AFTER APPROVED FLUSHING ON SUPPLY TUBING AND CONFIRM NO LEAKAGE AT DBL 90 DEGREE OVERHEAD AT RELOCATED PUMP STATION
07/22/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE TESTING PER PLAN
2) PROVIDE STAINLESS STEEL PIPING PER SPEC. ON PLAN
3) SUPPORT PIPING PER TABLE 3-1 94 UPC AND AT FITTINGS AND CHANGES OF DIRECTION. CHECK MANUFACTURERS INSTALLATION DIRECTION FOR SUPPORT OF PIPING