Permit Details

Status:
Expired
Type:
SINGLE FAMILY ADDITION
Address:
4590 S LAREDO CT
Address NEW:
4590 S LAREDO CT
Apply Date:
03/03/2005
Applicant:
JOSH CREAMER
Description:
ADDITION:PORCH/LAUNDRY ROOM

Permit Reviews

Permit Number - T05CM00974
Permit Status: Expired
Permit Description: ADDITION:PORCH/LAUNDRY ROOM
Start Date Submittal Complete Date Status  
03/03/2005 RESIDENTIAL BLDG/ZONING-WALKTHRU 06/17/2005 COMPLETED Review Details
03/06/2006 REVISION - WALK THRU 03/06/2006 ACTIVE Review Details
06/17/2005 RESUBMITTAL 07/06/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM00974
Permit Status: Expired
Permit Description: ADDITION:PORCH/LAUNDRY ROOM
Total Outstanding Activity Conditions - 1
Date Name
03/03/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05CM00974
Permite Description: ADDITION:PORCH/LAUNDRY ROOM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
BUILDING - FINAL N/A Not Inspected
02/28/2006 EXT METAL CLIPS/EXT SHEATHING N/A Partial Approval IVRS - Inspection :*
1) BLOCK UNDER JOINT ROOF DECK, AT GLU LAM 45 DEGREE ANGLE AND NAIL ENDS
2) IS SLOPE 1/4" PER FT. ?
3) HANGER AT 45 DEGREE GLU LAM IS UNDER SIZE ASK PLAN INSPECTOR TO CALC LOAD
4) 2 X 6 RAFTERS AT JOINT TO 45 DEGREE GLU LAM OVER 6'-0" LONG NEED SCKEWED RAFTER HANGER REQUIRED
5) MAKE SURE ROOF DECKING IS NAILED TO LEDGER AT 6" ON CENTER
6) NOTE 2" DRAIN FOR WASHER IS TO BE SLOPED AT 1/4" PER FT.

Completed Inspections

Permit Status: Expired
Permit Number: T05CM00974
Permit Description: ADDITION:PORCH/LAUNDRY ROOM
Total Completed Inspections - 9
Date Description Inspector Results Comments
02/02/2006 BUILDING PRE-SLAB WNORTH Approved IVRS - Inspection :*
02/02/2006 EXCAVATION/LAYOUT REBAR & ZON WNORTH Approved IVRS - Inspection :*
03/07/2006 ROOF NAILING RFREIDIN Approved IVRS - Inspection :*
03/10/2006 PLUMBING - INTERMEDIATE RFREIDIN Approved IVRS - Inspection :*
03/10/2006 ELECTRIC - INTERMEDIATE RFREIDIN Approved IVRS - Inspection :*
03/10/2006 FRAMING RFREIDIN Approved IVRS - Inspection :*
04/17/2006 PLUMBING - FINAL RFREIDIN Approved IVRS - Inspection :*
04/17/2006 PLUMBING - ROUGH, SOIL RFREIDIN Approved IVRS - Inspection :*
04/17/2006 ELECTRIC - FINAL RFREIDIN Approved IVRS - Inspection :*

Documents

File Name Document Type  
T05CM00974-1 2025 MASS-UPLOAD.PDF DOCUMENTS VIEW
T05CM00974 2025 MASS-UPLOAD.PDF DOCUMENTS VIEW