Permit: T05CM00873

Parcel: 11507315B


Addresses:

25 E DRACHMAN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/14/2005 ELECTRIC - FINAL Approved NEED APPROVED LISTING ON DEHUMIDIFIER. FINAL SUBJECT TO ETL LISTING ON DEHUMIDIFIER. I WAS ASKED OT RELEASE POWER BY DAVE MANN WHILE THIS WAS GOING ON
05/05/2005 ELECTRIC - FINAL Approved OK FOR POWER PER RAY MAJUTA
04/21/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK TEMP C OF O PER DAVE MANN 90 DAYS PENDING ETL LISTING
04/05/2005 ELECTRIC - FINAL Denied IVRS - Inspection :#1 NO VERIFICATION ON UNIT SUCH AS UL #2 EX FAN IN ROOM SHOULD GO TO PANEL-NO CIRCUIT FOR EX? MARKED IN PANEL C
04/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) COULD NOT FIND A TESTING LAB APPROVAL FOR DEHUMIDIFIER UNIT SUCH AS UL OR OTHER, FOUND PARTS LISTING AND ENCLOSURE LISTING. NO WHOLE UNIT LISTING. 2) SMALL LUG WHICH TIES UFER TO NEUTRAL GROUND LUG TO HAVE FULL SEATING OF FRONT HALF OF LUG NO JUST ON A 1/4"-20 NUT. 3) DISCONNECTS FOR EQUIPMENT MUST BE MARKED PERMANENTLY. 4) UNABLE TO GET TO ROOF TO CHECK EX ??. WAS ANY WORK DONE INSIDE NEW?