Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2005 | ELECTRIC - FINAL | Approved | NEED APPROVED LISTING ON DEHUMIDIFIER. FINAL SUBJECT TO ETL LISTING ON DEHUMIDIFIER. I WAS ASKED OT RELEASE POWER BY DAVE MANN WHILE THIS WAS GOING ON | |
| 05/05/2005 | ELECTRIC - FINAL | Approved | OK FOR POWER PER RAY MAJUTA | |
| 04/21/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TEMP C OF O PER DAVE MANN 90 DAYS PENDING ETL LISTING |
|
| 04/05/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection :#1 NO VERIFICATION ON UNIT SUCH AS UL #2 EX FAN IN ROOM SHOULD GO TO PANEL-NO CIRCUIT FOR EX? MARKED IN PANEL C | |
| 04/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COULD NOT FIND A TESTING LAB APPROVAL FOR DEHUMIDIFIER UNIT SUCH AS UL OR OTHER, FOUND PARTS LISTING AND ENCLOSURE LISTING. NO WHOLE UNIT LISTING. 2) SMALL LUG WHICH TIES UFER TO NEUTRAL GROUND LUG TO HAVE FULL SEATING OF FRONT HALF OF LUG NO JUST ON A 1/4"-20 NUT. 3) DISCONNECTS FOR EQUIPMENT MUST BE MARKED PERMANENTLY. 4) UNABLE TO GET TO ROOF TO CHECK EX ??. WAS ANY WORK DONE INSIDE NEW? |