Permit Details

Status:
Si_xpire
Type:
COMMERCIAL OTHER
Address NEW:
6422 E SPEEDWAY BL
Apply Date:
12/12/2005
Applicant:
N/A
Description:
CUT 40CY FILL 120CY
Contractors:
  • CAYLOR CONSTRUCTION COMPANY , RO

Permit Reviews

Permit Number - T05BU02920
Permit Status: Si_xpire
Permit Description: CUT 40CY FILL 120CY
Start Date Submittal Complete Date Status  
03/12/2007 REVISION - GRADING 03/12/2007 COMPLETED Review Details
03/15/2006 RESUBMITTAL - GRADING ALL 03/29/2006 COMPLETED Review Details
06/09/2006 RESUBMITTAL - GRADING 06/09/2006 COMPLETED Review Details
12/12/2005 PLANS OK TO SUBMIT - GRADING 12/12/2005 COMPLETED Review Details
12/12/2005 GRADING 01/25/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05BU02920
Permit Status: Si_xpire
Permit Description: CUT 40CY FILL 120CY
Total Outstanding Activity Conditions - 3
Date Name
12/12/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.
01/11/2006 Grading bond not to be released until the percolation results for the sub-surface ret./det. basins have been accepted by COT engineering. PM.
03/24/2006 To: Robert Caylor DATE: March 24, 2006 Robert Caylor Construction 6711 E. Speedway Blvd. Tucson, Arizona 85715 SUBJECT: Caylor Office Plaza, 6422 E. Speedway Blvd. Grading Plan T05BU02920(Second Review) T14S, R15E, Section 07 RESUBMITTAL REQUIRED: Drainage Report. The Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Grading Plan: 1. Percolation tests shall be performed prior to and after the installation of the sub-surface storage tank. 2. The Certificate of Occupancy will not be approved until the results of the percolation tests have been accepted. Drainage report: 1. Please include a response letter to the comments along with the corrected copies of the DR. 2. Re-submit the DR with the percolation test incorporated within the text. 3. The percolation test shall be performed prior to and after the installation of the sub-surface storage tank. 4. The Certificate of Occupancy will not be approved until the results of the percolation tests have been accepted. Stormwater pollution prevention plan: 1. The SWPPP has been accepted. If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax C:/6402 E. Speedway Blvd Grad3

Completed Inspections

Permit Status: Si_xpire
Permit Number: T05BU02920
Permit Description: CUT 40CY FILL 120CY
Total Completed Inspections - 9
Date Description Inspector Results Comments
12/13/2006 GRADING - INTERMEDIATE JBRUCKME Approved I LEFT A MESSAGE FOR ROB CAYLOR
1. TRASH ENCLOSURE IS NOT CONSTRUCTED PER PLAN, IT IS 9'4" SQUARE INSIDE, SHOULD BE 10' SQUARE INSIDE BOLLARDS AND GATE.
2. THERE ARE (4) HANDICAP PARKING SPACES STRIPED, BUT ONLY ONE RAMP.
3. LANDSCAPED AREAS MUST BE DEPRESSED 6" FOR WATER HARVESTING, OK NOW BUT LANDSCAPERS MAY SPREAD SPOIL OUT AND REDUCE, I NOTIFIED LANDSCAPE FOREMAN.
2. NEED
12/13/2006 STORMWATER FOLLOW-UP INSP JBRUCKME Approved NO STORMWATER CONCERNS
02/02/2007 NPPO PRE PERMIT INSPECTION ACONNOR Approved
02/02/2007 LANDSCAPE INSPECTION ACONNOR Approved
02/05/2007 STORMWATER FINAL INSPECTION JBRUCKME Approved
02/05/2007 STORMWATER INSTALL OF CONTROLS JBRUCKME Approved
02/05/2007 ENGINEERING PRE-CONSTRUCTION JBRUCKME Approved
03/16/2007 GRADING - FINAL JBRUCKME Approved
03/12/2008 PERMIT FINALED LJACKSON Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
2007_12_03_REVISION_001.TIF GRADING PLANS VIEW