Permit: T04PL01594
Permit Details
Apply Date:
09/01/2004
Applicant:
O HANLON EDWARD & PATRICIA CP/RS
Description:
REPAIR:GAS LINE
Permit Reviews
Permit Number - T04PL01594
Permit Status: Final
Permit Description: REPAIR:GAS LINE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/01/2004 | PLUMBING | 09/01/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04PL01594
Permit Status: Final
Permit Description: REPAIR:GAS LINE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/01/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T04PL01594
Permit Description: REPAIR:GAS LINE
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/03/2004 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :*/10PSI AIR TEST ON NEW PIPING SCOTCH COAT APP. 8' UNDERGROUND TO EXISTING PIPING TO BUILDING OVERHEAD TO WATER HEATER & FURANCE OK 1)PROVIDE BONDING OF BUILDING GAS PIPING 2)SOAL PENETRATION AT WATER HEATER AREA 3)EXTEND VENT FROM WATER HEATER 3' ABOVE COOLER INTAKE AND SCREW CAP ON TO VENT PIPE 4)WATER HEATER T & P TO GRAVITY DRAIN TO DAYLIGHT 03090-NOT READY |
| 09/09/2004 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :*/CORRECTION MADE |
| 09/09/2004 | PLUMBING - GAS PRESS TEST FNL | RRICH | Approved | IVRS - Inspection :* |
| 04/11/2005 | PERMIT FINALED | LJACKSON | Approved |