Permit: T04PL00986
Permit Details
Apply Date:
06/07/2004
Applicant:
NORTHERN PIPELINE CONSTRUCTION*C
Description:
REPLACE:GASLINE (APA)
Contractors:
- NORTHERN PIPELINE CONSTRUCTION*C
Outstanding Activity Conditions
Permit Number - T04PL00986
Permit Status: Expired
Permit Description: REPLACE:GASLINE (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/07/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04PL00986
Permite Description: REPLACE:GASLINE (APA)
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2004 | PLUMBING - GAS PRESSURE TEST | N/A | Partial Approval | IVRS - Inspection :* |
| 06/08/2004 | PLUMBING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :*/ PROVIDE RIGHT/LEFT NIPPLE AND COUPLING FOR CONNECTION TO BLD SERVICE LOCATION. 12 PSI AIR TEST ON NEW 1" FROM NEW METER LOCATION TO CAPPED LINE PRIOR TO SERVICE ENTRY OK. METER IS STILL ON. 1) PROVIDE APPROVED CAP FOR VENT FROM WTR HTR. 2) PROVIDE BONDING OF BLD GAS PIPING. 3) VENT FROM FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 2' ABOVE TOP OF COOLER. 4) PROVIDE APPROVED AGA OR CSA GAS VALVES AT ALL APPLIANCES. 5) PROVIDE ACCESS FOR WTR HTR INSP. |