Permit: T04PL00986

Parcel: 130030280


Addresses:

2714 E 23RD ST

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/08/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ PROVIDE RIGHT/LEFT NIPPLE AND COUPLING FOR CONNECTION TO BLD SERVICE LOCATION. 12 PSI AIR TEST ON NEW 1" FROM NEW METER LOCATION TO CAPPED LINE PRIOR TO SERVICE ENTRY OK. METER IS STILL ON. 1) PROVIDE APPROVED CAP FOR VENT FROM WTR HTR. 2) PROVIDE BONDING OF BLD GAS PIPING. 3) VENT FROM FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 2' ABOVE TOP OF COOLER. 4) PROVIDE APPROVED AGA OR CSA GAS VALVES AT ALL APPLIANCES. 5) PROVIDE ACCESS FOR WTR HTR INSP.