Permit: T04OT00377
Permit Details
Apply Date:
02/24/2004
Applicant:
BOB'S NEON
Description:
SIGN:#6767
Contractors:
- BOB'S NEON
Outstanding Inspections
Permit Status: Expired
Permit Number: T04OT00377
Permite Description: SIGN:#6767
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2004 | SIGN SHOP | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) LABEL IS NOT LEDGIABLE PLEASE FILL OUT WITH A PERMANENT MARKER 2) BOND RACEWAY ENCLOSURES 3) SUPPORT GTO CABLES UP OFF OF RACEWAY 4) ELECTOBIT BOOTS ARE SPLIT 5) RESUPPORT GLASS TO LETTER HOUSEING 6) SWITCH TO BE WITHIN SITE OF SIGN OR A LOCK OUT IS NEEDED 600.6 7) SUPPORT CONDUIT UP OFF OF ROOF AND TIGHTEN LOOSE FITTINGS-NO MORE THAN 360 DEGREE IN A RUN AND NO KINKS 8) A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 9) NO MORE THAN (1) ONE TERMINATION PER NEUTRAL LUG 10) PLEASE VERIFY LICENSED L-11 CONTRACTOR WHO RAN SIGN CIRCUIT |
10/25/2004 | SIGN ELECTRIC | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
Completed Inspections
Permit Status: Expired
Permit Number: T04OT00377
Permit Description: SIGN:#6767
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/26/2004 | SIGN SITE REVIEW | JSONKIN | Approved | |
10/08/2004 | SIGN INSPECTION | RDEAR | Approved | IVRS - Inspection :* |