Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04OT00377

Parcel: 12212012A


Addresses:

4551 E SPEEDWAY BL


Inspection Status: Denied

Inspection History: SIGN SHOP

Permit Number - T04OT00377

Inspection Description - SIGN SHOP

Inspection Status - Denied

Date Description Inspector Results Comments
10/25/2004 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) LABEL IS NOT LEDGIABLE PLEASE FILL OUT WITH A PERMANENT MARKER 2) BOND RACEWAY ENCLOSURES 3) SUPPORT GTO CABLES UP OFF OF RACEWAY 4) ELECTOBIT BOOTS ARE SPLIT 5) RESUPPORT GLASS TO LETTER HOUSEING 6) SWITCH TO BE WITHIN SITE OF SIGN OR A LOCK OUT IS NEEDED 600.6 7) SUPPORT CONDUIT UP OFF OF ROOF AND TIGHTEN LOOSE FITTINGS-NO MORE THAN 360 DEGREE IN A RUN AND NO KINKS 8) A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 9) NO MORE THAN (1) ONE TERMINATION PER NEUTRAL LUG 10) PLEASE VERIFY LICENSED L-11 CONTRACTOR WHO RAN SIGN CIRCUIT