Permit: T04ME00374
Permit Details
Apply Date:
06/07/2004
Applicant:
PUEBLO HEATING & COOLING INC *C
Description:
INSTALL:3 1/2TON SYSTEM (APA)
Contractors:
- PUEBLO HEATING & COOLING INC *C
Outstanding Activity Conditions
Permit Number - T04ME00374
Permit Status: Expired
Permit Description: INSTALL:3 1/2TON SYSTEM (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/07/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04ME00374
Permite Description: INSTALL:3 1/2TON SYSTEM (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2004 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ DBL WALL VENT FROM FURNACE AND WTR HTR IS TERMINATED INTO A SINGLE WALL TEE. CHANGE DBL WALL PIPE TO SINGLE WALL OR CHANGE TEE TO DBL WALL. DO NOT USE TAPE. PLUG UNUSED CONDENSATE OUTLET ON COIL. PROVIDE HOSE CLAMPS ON BOTH ENDS OF PLASTIC CONDENSATE HOSE. TIGHTEN ROMEX CONNECTORS ONTO POWER CORDS AND ATTACHMENT TO FURNACE COMPARTMENTS. SEAL AROUND REFER LINE PENETRATION. DO NOT USE A G.E. BREAKER IN A SIEMANS PANEL. YOU CAN ONLY USE SIEMANS BREAKERS. |