Permit: T04ME00305
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
9020 E BERKSHIRE PL
Address NEW:
9020 E BERKSHIRE PL
Apply Date:
05/13/2004
Applicant:
G T R HEATING AND AIR COND,*C
Description:
REPLACE:A/C & FURNACE (APA)
Contractors:
- G T R HEATING AND AIR COND,*C
Outstanding Activity Conditions
Permit Number - T04ME00305
Permit Status: Expired
Permit Description: REPLACE:A/C & FURNACE (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/13/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04ME00305
Permite Description: REPLACE:A/C & FURNACE (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2004 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ PROVIDE A TRAP ON CONDENSATE DRAIN LINE. 3/8" I.D. X 12" GAS FLEX NOT ADEQUATE FOR 110,000 BTU. THE DAMPER FOR THE EVAP COOLER MUST BE INSTALLED ABOVE THE FURNACE TO PREVENT DAMP AIR FROM RUSTING THE HEAT EXCHANGER AND OTHER COMPONANTS INSIDE THE FURNACE. PROVIDE CLEARANCE WHERE VENT CONNECTOR IS IS TOUCHING RUBATEX. |