Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ PROVIDE A TRAP ON CONDENSATE DRAIN LINE. 3/8" I.D. X 12" GAS FLEX NOT ADEQUATE FOR 110,000 BTU. THE DAMPER FOR THE EVAP COOLER MUST BE INSTALLED ABOVE THE FURNACE TO PREVENT DAMP AIR FROM RUSTING THE HEAT EXCHANGER AND OTHER COMPONANTS INSIDE THE FURNACE. PROVIDE CLEARANCE WHERE VENT CONNECTOR IS IS TOUCHING RUBATEX. |