Permit: T04ME00178
Permit Details
Apply Date:
04/02/2004
Applicant:
D AND H AIR CONDITIONING CO,*C
Description:
REPLACE:GAS PACK (APA)
Contractors:
- D AND H AIR CONDITIONING CO,*C
Outstanding Activity Conditions
Permit Number - T04ME00178
Permit Status: Expired
Permit Description: REPLACE:GAS PACK (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/02/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04ME00178
Permite Description: REPLACE:GAS PACK (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2004 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ EMT FITTING STILL HAS NOT BEEN REMOVED FROM INSIDE THE ELEC. PANEL OR THE DISCONNECT. PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION. ALSO YOU CANNOT USE #8 WIRE ON A 60 AMP CIRCUIT. CHANGE CIRCUIT BREAKER TO A SMALLER SIZE OR CHANGE WIRE TO #6. RECALL FOR INSP. |