Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ EMT FITTING STILL HAS NOT BEEN REMOVED FROM INSIDE THE ELEC. PANEL OR THE DISCONNECT. PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION. ALSO YOU CANNOT USE #8 WIRE ON A 60 AMP CIRCUIT. CHANGE CIRCUIT BREAKER TO A SMALLER SIZE OR CHANGE WIRE TO #6. RECALL FOR INSP. |
|
| 05/05/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920*/ NOBODY HOME. HAVE YOUR CONTRACTOR RECALL. PLEASE LEAVE CUTOMERS NO. WHEN YOU SCHEDULE THE NEXT INSP. |
|
| 04/23/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) YOU CANNOT USE AN EMT FITTING TO CONNECT AN LB TO THE CIRCUIT PANEL. 2) TIGHTEN ROMEX CONNECTOR ONTO POWER CORD FOR FURNACE. PROVIDE A ROMEX CONNECTOR WHERE CONDENSATE PUMP CORD ENTERS FURNACE. RECALL FOR INSP. |
|
| 04/20/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0920*/ 1) PLEASE HAVE YOUR CONTRACTOR CALL FOR AN INSPECTION WHEN SOMEONE WILL BE HOME |