Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
03/12/2004
Applicant:
TRI CITY MECHANICAL INC , *C
Description:
REPLACE:3 GAS PACKS (APA)
Contractors:
  • TRI CITY MECHANICAL INC , *C

Outstanding Activity Conditions

Permit Number - T04ME00121
Permit Status: Expired
Permit Description: REPLACE:3 GAS PACKS (APA)
Total Outstanding Activity Conditions - 1
Date Name
03/12/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04ME00121
Permite Description: REPLACE:3 GAS PACKS (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
03/26/2004 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*/ UNITS #5 AND #6 - 1) PROVIDE AN AGA APPROVED GAS SHUT OFF VALVE IMMEDIATLY PRECEEDING THE UNION IN THE GAS LINE. 2) SECURE THE ELEC. DISCONNECTS AND FILL ANY UNUSED OPENINGS INTO DISCONNECTS. 3) BLOCK AND CLAMP NEW SECTIONS OF GAS LINES. / UNIT #1 - ALL OF THE ABOVE PLUS SUPPORT CONDENSATE DRAIN LINE AND PAINT WITH LATEX PAINT.