Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00121
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ UNITS #5 AND #6 - 1) PROVIDE AN AGA APPROVED GAS SHUT OFF VALVE IMMEDIATLY PRECEEDING THE UNION IN THE GAS LINE. 2) SECURE THE ELEC. DISCONNECTS AND FILL ANY UNUSED OPENINGS INTO DISCONNECTS. 3) BLOCK AND CLAMP NEW SECTIONS OF GAS LINES. / UNIT #1 - ALL OF THE ABOVE PLUS SUPPORT CONDENSATE DRAIN LINE AND PAINT WITH LATEX PAINT. |