Permit: T04ME00121

Parcel: 126070720


Addresses:

3901 E BROADWAY BL


Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Permit Number - T04ME00121

Inspection Description - MECHANICAL - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
03/26/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ UNITS #5 AND #6 - 1) PROVIDE AN AGA APPROVED GAS SHUT OFF VALVE IMMEDIATLY PRECEEDING THE UNION IN THE GAS LINE. 2) SECURE THE ELEC. DISCONNECTS AND FILL ANY UNUSED OPENINGS INTO DISCONNECTS. 3) BLOCK AND CLAMP NEW SECTIONS OF GAS LINES. / UNIT #1 - ALL OF THE ABOVE PLUS SUPPORT CONDENSATE DRAIN LINE AND PAINT WITH LATEX PAINT.