Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
5540 E 22ND ST
Address NEW:
5540 E 22ND ST
Apply Date:
01/20/2004
Applicant:
JETT MECHANICAL L L C
Description:
REPLACE:2 GAS PACKS
Contractors:
  • JETT MECHANICAL L L C

Permit Reviews

Permit Number - T04ME00023
Permit Status: Expired
Permit Description: REPLACE:2 GAS PACKS
Start Date Submittal Complete Date Status  
01/20/2004 MECHANICAL 01/20/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04ME00023
Permit Status: Expired
Permit Description: REPLACE:2 GAS PACKS
Total Outstanding Activity Conditions - 1
Date Name
01/20/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04ME00023
Permite Description: REPLACE:2 GAS PACKS
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
02/18/2004 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*/ 1) PROVIDE OUTSIDE AIR INTAKES ON A/C UNITS. BE SURE TO MAINTAIN 10' AWAY FROM ALL EXHAUST VENTS. 2) ½" I.D. GAS FLEX NOT ADEQUATE FOR 300,000 BTU. 3) PERMANENTLY LABEL UNITS WITH UNIT NO. RECALL FOR INSPECTION.