Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/18/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE OUTSIDE AIR INTAKES ON A/C UNITS. BE SURE TO MAINTAIN 10' AWAY FROM ALL EXHAUST VENTS. 2) ½" I.D. GAS FLEX NOT ADEQUATE FOR 300,000 BTU. 3) PERMANENTLY LABEL UNITS WITH UNIT NO. RECALL FOR INSPECTION. |
| 02/03/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ PVC EXPOSED ON ROOF, NEEDS TO BE PAINTED. |