Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T04ME00023
Permit Details
Apply Date:
01/20/2004
Applicant:
JETT MECHANICAL L L C
Description:
REPLACE:2 GAS PACKS
Contractors:
- JETT MECHANICAL L L C
Permit Reviews
Permit Number - T04ME00023
Permit Status: Expired
Permit Description: REPLACE:2 GAS PACKS
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/20/2004 | MECHANICAL | 01/20/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04ME00023
Permit Status: Expired
Permit Description: REPLACE:2 GAS PACKS
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
01/20/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04ME00023
Permite Description: REPLACE:2 GAS PACKS
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/18/2004 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999*/ 1) PROVIDE OUTSIDE AIR INTAKES ON A/C UNITS. BE SURE TO MAINTAIN 10' AWAY FROM ALL EXHAUST VENTS. 2) ½" I.D. GAS FLEX NOT ADEQUATE FOR 300,000 BTU. 3) PERMANENTLY LABEL UNITS WITH UNIT NO. RECALL FOR INSPECTION. |