Permit: T04EL02516
Permit Details
Apply Date:
12/29/2004
Applicant:
CARLOS M ARIAS
Description:
RECONNECT:ELECTRIC:APARTMENT
Outstanding Activity Conditions
Permit Number - T04EL02516
Permit Status: Closed
Permit Description: RECONNECT:ELECTRIC:APARTMENT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/29/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T04EL02516
Permite Description: RECONNECT:ELECTRIC:APARTMENT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - RECONNECT | N/A | Not Inspected | ||
| 01/03/2005 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES 1) INSTALL PERMANENT ADDRESS LABEL ON ELECT SERVICE. NO MARKING PEN. 2) INSTALL BUSHING WHERE WIRES PASS THRU DISCONNECT SWITCH INTO BLDG. 3) GROUNDING ELECTRODE CONDUCTOR CUT, NO WATER & GAS BOND. 4) RISER CONDUCTORS TO SHORT TO BE RE ATTACHED TO SERVICE DROP. 5) WIRING INSIDE AT SUB PANEL NOT WIRED PROPERLY. 6) RANGE HOOD NOT WIRED PROPERLY 7) INSTALL SMOKE DETECTORS IN BEDROOMS. 8) REPAIR BROKEN RECEPTACLES &LIGHT SWITCHES, LIGHT FIXTURES. COOLER MUST HAVE W/P BOX WITH COVER FOR PLUGS. WORK MUST BE DONE PER CODE , USE C-11 LICENSED CONTRACTOR. |