Permit Details

Status:
Closed
Type:
MULTI FAMILY OTHER
Address NEW:
5151 S 12TH AV #02
Apply Date:
12/29/2004
Applicant:
CARLOS M ARIAS
Description:
RECONNECT:ELECTRIC:APARTMENT

Outstanding Activity Conditions

Permit Number - T04EL02516
Permit Status: Closed
Permit Description: RECONNECT:ELECTRIC:APARTMENT
Total Outstanding Activity Conditions - 1
Date Name
12/29/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T04EL02516
Permite Description: RECONNECT:ELECTRIC:APARTMENT
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
ELECTRIC - RECONNECT N/A Not Inspected
01/03/2005 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES 1) INSTALL PERMANENT ADDRESS LABEL ON ELECT SERVICE. NO MARKING PEN. 2) INSTALL BUSHING WHERE WIRES PASS THRU DISCONNECT SWITCH INTO BLDG. 3) GROUNDING ELECTRODE CONDUCTOR CUT, NO WATER & GAS BOND. 4) RISER CONDUCTORS TO SHORT TO BE RE ATTACHED TO SERVICE DROP. 5) WIRING INSIDE AT SUB PANEL NOT WIRED PROPERLY. 6) RANGE HOOD NOT WIRED PROPERLY 7) INSTALL SMOKE DETECTORS IN BEDROOMS. 8) REPAIR BROKEN RECEPTACLES &LIGHT SWITCHES, LIGHT FIXTURES. COOLER MUST HAVE W/P BOX WITH COVER FOR PLUGS. WORK MUST BE DONE PER CODE , USE C-11 LICENSED CONTRACTOR.

Documents

File Name Document Type  
None DOCUMENTS VIEW