Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T04EL02446
Permit Details
Apply Date:
12/14/2004
Applicant:
GEORGE JACKSON
Description:
RECONNECT:ELECTRIC:GUEST HOUSE & UPGRADE
Permit Reviews
Permit Number - T04EL02446
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC:GUEST HOUSE & UPGRADE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
06/07/2005 | ELECTRICAL | 06/07/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04EL02446
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC:GUEST HOUSE & UPGRADE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
12/14/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL02446
Permite Description: RECONNECT:ELECTRIC:GUEST HOUSE & UPGRADE
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/10/2005 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1) SERVICE DISCONNECT TO HIGH AFF, RELOCATE TO A MAXIMUM HEIGHT OF 6' -OCCUPANT MUST BE ABLE TO REACH IN EVENT OF EMERGENCY. 2) RAISE SMOKE DETECTOR TO 6" TO 12" BELOW CEILING, 3) INSTALL MISSING LIGHT FIXTURES, COVER PLATES, 4) INSTALL PERMANENT ADDRESS LABE ON SERVICE ENCLOSURE. |
06/03/2005 | ELECTRIC - RECONNECT | N/A | Partial Approval | IVRS - Inspection :* OK TO CLEAR INC #2. OK ITEMS CORRECTED OK TO FINAL AFTER SERVICE UPGRADE ADDED TO THIS PERMIT |