Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL02446
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/10/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1) SERVICE DISCONNECT TO HIGH AFF, RELOCATE TO A MAXIMUM HEIGHT OF 6' -OCCUPANT MUST BE ABLE TO REACH IN EVENT OF EMERGENCY. 2) RAISE SMOKE DETECTOR TO 6" TO 12" BELOW CEILING, 3) INSTALL MISSING LIGHT FIXTURES, COVER PLATES, 4) INSTALL PERMANENT ADDRESS LABE ON SERVICE ENCLOSURE. |