Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
1010 E 6TH ST
Address NEW:
1010 E 6TH ST
Apply Date:
12/13/2004
Applicant:
JAMES INNERS
Description:
RECONNECT:ELECTRIC

Outstanding Activity Conditions

Permit Number - T04EL02437
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC
Total Outstanding Activity Conditions - 1
Date Name
12/13/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Expired
Permit Number: T04EL02437
Permit Description: RECONNECT:ELECTRIC
Total Completed Inspections - 2
Date Description Inspector Results Comments
12/15/2004 ELECTRIC - FINAL RMAJUTA Approved 1) THE 60 AMP DISCONNECT MAIN DOES NOT ENGAGE FULLY, THE DISCONNECT DOES NOT WORK PROPERLY
2) DBL LUGGING AT LOAD SIDE OF DISCONNECT IS NOT ALLOWED
3) THE TERMINAL AND CONDUCTOR ON LINE SIDE LH IS CORRODED AND BEGINING TO CRYSTALIZE (SIGNS OF DETERIORATION AND AGE. NEUTRAL WIRE ON LOAD SIDE ALSO IN SAME CONDITION
4) THE GROUND ROD CLAMP TO SERVICE HAS BEEN DISCONNECTED
5) THE RISER IS NOT SUPPORTED
6) DISCONNECT CIRCUIT INTO BLDG FROM MAIN BECAUSE IT'S NOT BEING USED
02/09/2005 TEP CLEARANCE - AM RMAJUTA Approved OK RECON PER MAJUTA

Documents

File Name Document Type  
T04EL02437 2025 MASS-UPLOAD.PDF DOCUMENTS VIEW
T04EL02437 ARC.PDF DOCUMENTS VIEW