Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/08/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND ROD BELOW SERVICE REQUIED TO BE FLUSH OR BELOW GARDE PER CODE USE ACORN CLAMP TYPE SUITABLE FOR BURIAL. 2) CONNECT LOAD FROM SPACE 1010 S PARK TO THIS PANEL. 3) SPACE TO BE OPEN FOR INSPECTION. |
|
| 12/15/2004 | ELECTRIC - FINAL | Denied | 1) THE 60 AMP DISCONNECT MAIN DOES NOT ENGAGE FULLY, THE DISCONNECT DOES NOT WORK PROPERLY 2) DBL LUGGING AT LOAD SIDE OF DISCONNECT IS NOT ALLOWED 3) THE TERMINAL AND CONDUCTOR ON LINE SIDE LH IS CORRODED AND BEGINING TO CRYSTALIZE (SIGNS OF DETERIORATION AND AGE. NEUTRAL WIRE ON LOAD SIDE ALSO IN SAME CONDITION 4) THE GROUND ROD CLAMP TO SERVICE HAS BEEN DISCONNECTED 5) THE RISER IS NOT SUPPORTED 6) DISCONNECT CIRCUIT INTO BLDG FROM MAIN BECAUSE IT'S NOT BEING USED |
|
| 12/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/LEAVE A PHONE #. 623-4747 CALLED AND LEFT MESSAGE UNIT MUST BE OPEN. MOVE ALL ITEMS FROM IN FRONT OF SERVICE TO MAKE INSPECTION |