Permit: T04EL02437

Parcel: 124052040


Addresses:

1010 E 6TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/09/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/08/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) GROUND ROD BELOW SERVICE REQUIED TO BE FLUSH OR BELOW GARDE PER CODE USE ACORN CLAMP TYPE SUITABLE FOR BURIAL. 2) CONNECT LOAD FROM SPACE 1010 S PARK TO THIS PANEL. 3) SPACE TO BE OPEN FOR INSPECTION.
12/15/2004 ELECTRIC - FINAL Denied 1) THE 60 AMP DISCONNECT MAIN DOES NOT ENGAGE FULLY, THE DISCONNECT DOES NOT WORK PROPERLY
2) DBL LUGGING AT LOAD SIDE OF DISCONNECT IS NOT ALLOWED
3) THE TERMINAL AND CONDUCTOR ON LINE SIDE LH IS CORRODED AND BEGINING TO CRYSTALIZE (SIGNS OF DETERIORATION AND AGE. NEUTRAL WIRE ON LOAD SIDE ALSO IN SAME CONDITION
4) THE GROUND ROD CLAMP TO SERVICE HAS BEEN DISCONNECTED
5) THE RISER IS NOT SUPPORTED
6) DISCONNECT CIRCUIT INTO BLDG FROM MAIN BECAUSE IT'S NOT BEING USED
12/14/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/LEAVE A PHONE #. 623-4747 CALLED AND LEFT MESSAGE UNIT MUST BE OPEN. MOVE ALL ITEMS FROM IN FRONT OF SERVICE TO MAKE INSPECTION