Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
2117 S PALM SPRINGS DR
Apply Date:
11/26/2004
Applicant:
AMERICAN HOME MAINTENANCE INC *C
Description:
INSTALL:ELECTRIC CIRCUIT (APA)
Contractors:
  • AMERICAN HOME MAINTENANCE INC *C

Outstanding Activity Conditions

Permit Number - T04EL02353
Permit Status: Expired
Permit Description: INSTALL:ELECTRIC CIRCUIT (APA)
Total Outstanding Activity Conditions - 1
Date Name
11/26/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04EL02353
Permite Description: INSTALL:ELECTRIC CIRCUIT (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
11/30/2004 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED AN ELECTRICAL UPGRADE PERMIT
2) INSTALL GROUNDING BUSHING AT OFF SET NIPPLE IN METER BASE
3) INSTALL ANTI-OXIDATION PASTE AT ALL ALUMINIUM TERMINATIONS
4) ALL PANEL PENETRATIONS NEED TO BE RAIN TIGHT ENTRYS WHERE HIGHER THAN THE BUS BAR ( 1/2" EMT AND 2" OFF SET NIPPLE)
5) SECURE 3/4" EMT FEEDING A/C PER NEC (ABOVE PANEL)
6) SEAL UNUSED PANEL OPENINGS (1/2" KNOCKOUT AT BOTTOM OF PANEL)
7) EXPOSE GROUND RODS (BOTH OF THEM)
8) BOND GAS PIPE TO ELECTRIC SERVICE
9) SECURE EMT WITHIN 3' OF LB
10) SEAL TIGHT SHOULD NOT BE USED IN LENGTHS GREATER THAN 6'