Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
135 S STRATFORD DR
Apply Date:
10/29/2004
Applicant:
BRIAN LAIRD
Description:
RECONNECT:ELECTRIC 3 METERS

Outstanding Activity Conditions

Permit Number - T04EL02195
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC 3 METERS
Total Outstanding Activity Conditions - 1
Date Name
10/29/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04EL02195
Permite Description: RECONNECT:ELECTRIC 3 METERS
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
11/10/2004 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/10/2004 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 139 S. STRATFORD DR: 1) LABEL BREAKER, BOND PANEL AND NEED A/C PERMIT
2) LABEL INTERIOR PANEL
3) NEED NEW FEEDER TO INTERIOR PANEL
4) PROPERLY GROUND ALL DEVICES
-----------------------------------------------------------------------------------------
145 S. STRATFORD DR: 1) NEED A/C PERMIT
2) LABEL PANEL BOARD
3) NEED NEW FEEDER TO PANEL BOARD
4) INPROPER CLEARANCE AT SUB PANEL
-----------------------------------------------------------------------------------------135 S. STRATFORD DR: 1) NEED SERVICE UPGRADE. SERVICE IS DAMAGED AND NOT SERVICEABLE. CLEANOUT IN FRONT OF SERVICE VIOLATES 110.26. OBTAIN UPGRADE PERMIT AND A/C PERMIT
2) PLEASE INDICATE OTHER SERVICES PER NEC 230.2 (E)
3) LABEL INTERIOR PANEL BOARDS WITH A PERMANENT TAG
4) WILL NEED A NEW FEEDER TO INTERIOR TO ACCOMADATE REPLACED PANEL BOARD AND EQUIPMENT GROUNDS FOR NEW ? BRANCH CIRCUITS
5) CHECK ALL DEVICES FOR PROPER GROUNDING

Completed Inspections

Permit Status: Expired
Permit Number: T04EL02195
Permit Description: RECONNECT:ELECTRIC 3 METERS
Total Completed Inspections - 1
Date Description Inspector Results Comments
11/05/2004 FIRE - FINAL LTHOMAS Approved