Permit: T04EL02046
Permit Details
Apply Date:
10/06/2004
Applicant:
PUEBLO ELECTRIC SERVICES *C
Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP (APA)
Contractors:
- PUEBLO ELECTRIC SERVICES *C
Outstanding Activity Conditions
Permit Number - T04EL02046
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/06/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL02046
Permite Description: UPGRADE:ELECTRIC 100AMP TO 200AMP (APA)
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2004 | ELECTRIC - UNDERGROUND | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 10/07/2004 | ELECTRIC - INTERMEDIATE | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 10/07/2004 | ELECTRIC - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :USE PERMANENT MEANS TO LABEL BREAKERS NOT PENCIL ENTRANCES ABOVE CURRENT CARRING PARTS TO BE SEALED USE APPROVED BONDING DEVICES BOTH SIDES OF SERVICE NIPPLE RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGED IN ANTIOXIDE COMPOUND NEEDED FOR ALUMINUM CONDUCTORS PLEASE UNCOVER GROUND ROD CONNECTIONS FOR INSPECTION WATER BOND TO BE INTERIOR SIDE OF UNIONS AND COUPLINGS TIGHTEN LOOSE FITTINGS AND LOCKNUTS WHAT IS SURGE PROTECTION BREAKER FOR? |