Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/07/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :USE PERMANENT MEANS TO LABEL BREAKERS NOT PENCIL
ENTRANCES ABOVE CURRENT CARRING PARTS TO BE SEALED
USE APPROVED BONDING DEVICES BOTH SIDES OF SERVICE NIPPLE
RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGED IN
ANTIOXIDE COMPOUND NEEDED FOR ALUMINUM CONDUCTORS
PLEASE UNCOVER GROUND ROD CONNECTIONS FOR INSPECTION
WATER BOND TO BE INTERIOR SIDE OF UNIONS AND COUPLINGS
TIGHTEN LOOSE FITTINGS AND LOCKNUTS
WHAT IS SURGE PROTECTION BREAKER FOR?