Permit Details

Status:
Withdrwn
Type:
SINGLE FAMILY OTHER
Address:
431 W ROSALES ST
Address NEW:
431 W ROSALES ST
Apply Date:
08/27/2004
Applicant:
MARINA TINEO
Description:
ELECTRIC:RECONNECT & INCREASE TO 150 AMP /GENERAL ELECTRICAL REPAIRS

Permit Reviews

Permit Number - T04EL01784
Permit Status: Withdrwn
Permit Description: ELECTRIC:RECONNECT & INCREASE TO 150 AMP /GENERAL ELECTRICAL REPAIRS
Start Date Submittal Complete Date Status  
11/08/2004 ELECTRICAL 11/08/2004 COMPLETED Review Details
11/08/2004 ELECTRICAL 11/08/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04EL01784
Permit Status: Withdrwn
Permit Description: ELECTRIC:RECONNECT & INCREASE TO 150 AMP /GENERAL ELECTRICAL REPAIRS
Total Outstanding Activity Conditions - 1
Date Name
08/27/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Withdrwn
Permit Number: T04EL01784
Permite Description: ELECTRIC:RECONNECT & INCREASE TO 150 AMP /GENERAL ELECTRICAL REPAIRS
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
08/30/2004 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection :The wiring is not complete or does not comply with code.| DOUBLE LUGGING AT SERVICE DISC NOT ALLOWED. DISCONNECT SERVICE NOT SUFFICENT FOR CIRCUITS REQUIRED FOR DWELLING, SERVICE SHOULD BE UPGRADED TO ACCOMODATE LOAD
COOLER NOT WIRED SAFELY, SPLICED WIRES & ZIP CORD NOT ALLOWED, INSTALL W/P RECEIPT OR MIDWEST COOLER BOX & USE APPROVED CORDS TO PLUG-IN PUMP-BLOWER MOTORS.
INTERIOR WIRING EXPOSED ROMEX & WIRING METHODS NOT PER CODE, USE OF LAMP CORD TO FEED CONVIENENCE OUTLETS NOT ALLOWED
EXPOSED ROMEX IN BACK OUTSIDE NOT ALLOWED
HAVE C-11 LICENSED CONTRACTOR TO REWIRE TO CODE. PROVIDE BETTER FLOOR PLAN & OBTAIN 1-HR ELECTRICAL REPAIR PERMIT
08/30/2004 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*