Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
Permit Number - T04EL01784
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ADDRESS LABEL ON SERVICE. 2) SERVICE NOT GROUNDED, WATER, & GAS PIPING NOT BONDED. 3) OUTSIDE RECEPT ?? BE GFI. 4) RISER CONDUIT NOT SUPPORTED WITHIN 3' OF ENCLOSURE. 5) MUST HAVE FUNCTIONAL HEATING & COOLING. 6) NEW WIRING INSIDE NOT PER CODE. HAVE C-11 LICENSED CONTR. CONTACT INSPECTOR PRIOR TO NEXT INSPECTION. 791-5550 EXT 1136. SEE NOTES LAST INSPECTION |
|
08/30/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| DOUBLE LUGGING AT SERVICE DISC NOT ALLOWED. DISCONNECT SERVICE NOT SUFFICENT FOR CIRCUITS REQUIRED FOR DWELLING, SERVICE SHOULD BE UPGRADED TO ACCOMODATE LOAD COOLER NOT WIRED SAFELY, SPLICED WIRES & ZIP CORD NOT ALLOWED, INSTALL W/P RECEIPT OR MIDWEST COOLER BOX & USE APPROVED CORDS TO PLUG-IN PUMP-BLOWER MOTORS. INTERIOR WIRING EXPOSED ROMEX & WIRING METHODS NOT PER CODE, USE OF LAMP CORD TO FEED CONVIENENCE OUTLETS NOT ALLOWED EXPOSED ROMEX IN BACK OUTSIDE NOT ALLOWED HAVE C-11 LICENSED CONTRACTOR TO REWIRE TO CODE. PROVIDE BETTER FLOOR PLAN & OBTAIN 1-HR ELECTRICAL REPAIR PERMIT |