Permit: T04EL01657
Permit Details
Apply Date:
08/10/2004
Applicant:
CAROL SHAUN MCMANIMON
Description:
SERVICE:ELECTRIC CONDUIT
Permit Reviews
Permit Number - T04EL01657
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC CONDUIT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/10/2004 | ELECTRICAL | 08/10/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04EL01657
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC CONDUIT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/10/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL01657
Permite Description: SERVICE:ELECTRIC CONDUIT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - FINAL | N/A | Not Inspected | ||
| 08/13/2004 | ELECTRIC - UNDERGROUND | N/A | Denied | IVRS - Inspection : The conduit is not installed per code.| 240* 1) REPLACE THE TORCH BURNED 90o ELL. USE FACTORY MADE 90'S OR 45s. 2) SUBMIT A PLAN SHOWING WHAT THE REDISTRIBUTION OF LOAD POWER IS GOING TO SERVE. 3) ALL PVC MUST HAVE A MINIMUM 18" OF COVER. FROM TOP OF PIPE TO FINISHED GRADE. |