Permit: T04EL01657

Parcel: 12504039A


Addresses:

2221 E 1ST ST

Inspection Status: Denied

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
08/13/2004 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The conduit is not installed per code.| 240*
1) REPLACE THE TORCH BURNED 90o ELL. USE FACTORY MADE 90'S OR 45s. 2) SUBMIT A PLAN SHOWING WHAT THE REDISTRIBUTION OF LOAD POWER IS GOING TO SERVE. 3) ALL PVC MUST HAVE A MINIMUM 18" OF COVER. FROM TOP OF PIPE TO FINISHED GRADE.