Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T04EL01247
Permit Details
Apply Date:
06/11/2004
Applicant:
SANDRA BROWN
Description:
POLE LIGHT CONVERTED FROM GAS TO ELECT/1 circuit
Permit Reviews
Permit Number - T04EL01247
Permit Status: Expired
Permit Description: POLE LIGHT CONVERTED FROM GAS TO ELECT/1 circuit
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
06/11/2004 | ELECTRICAL | 06/11/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04EL01247
Permit Status: Expired
Permit Description: POLE LIGHT CONVERTED FROM GAS TO ELECT/1 circuit
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/11/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL01247
Permite Description: POLE LIGHT CONVERTED FROM GAS TO ELECT/1 circuit
Total Outstanding Inspections - 3
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2004 | ELECTRIC - UNDERGROUND | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
06/21/2004 | ELECTRIC - INTERMEDIATE | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
06/21/2004 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) UF CABLE MUST BE PROTECTED FROM PHYSICAL DAMAGE WHERE IT IS INSTALLED ABOVE GROUND MUST BE PROTECTED WHERE IT ENTERS POLE LT. 2) LIGHT FIXTURE AT TOP OF POLE MUST BE LISTED. HOME MADE FIXTURE NOT APPROVED. 3) UNCOVER AND EXPOSE WIRE IN TRENCH FOR INSPECTION MUST BE AT LEAST 24" DEEP. |