Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL01247
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) UF CABLE MUST BE PROTECTED FROM PHYSICAL DAMAGE WHERE IT IS INSTALLED ABOVE GROUND MUST BE PROTECTED WHERE IT ENTERS POLE LT. 2) LIGHT FIXTURE AT TOP OF POLE MUST BE LISTED. HOME MADE FIXTURE NOT APPROVED. 3) UNCOVER AND EXPOSE WIRE IN TRENCH FOR INSPECTION MUST BE AT LEAST 24" DEEP. |