Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
4245 E 4TH ST
Address NEW:
4245 E 4TH ST
Apply Date:
05/24/2004
Applicant:
CORRECT CONNECTIONS INC *C
Description:
UPGRADE:ELECTRIC (APA)
Contractors:
  • CORRECT CONNECTIONS INC *C

Outstanding Activity Conditions

Permit Number - T04EL01090
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC (APA)
Total Outstanding Activity Conditions - 1
Date Name
05/24/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04EL01090
Permite Description: UPGRADE:ELECTRIC (APA)
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
06/18/2004 ELECTRIC - UNDERGROUND N/A Not ready for Inspection IVRS - Inspection :*
06/18/2004 ELECTRIC - INTERMEDIATE N/A Not ready for Inspection IVRS - Inspection :*
06/18/2004 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ARIEL CONDUCTORS TO BE INSTALLED PER 230-24 AND 110-14 - 8' OFF OF ROOF AND USE APPROVED SPLICE INSULATION. 2) GROUNDING ELECTRODE SYSTEM NEEDED AT 2ND STRUCTURE DISCONNECT. 3) DRYWALL SCREWS NOT ALLOWED FOR MOUNTING HARDWARE. 4) PLEASE VERIFY WTR AND GAS BONDS. 5) NM CABLE NOT ALLOWED IN A COMPLETE RACEWAY SYSTEM. 6) #8 THHN AMPACITY ONLY 50 AMPS. #8 NM CABLE AMPACITY ONLY 40 AMPS. 7) PLEASE VERIFY A/C PERMIT FOR NEW SERVICE.

Documents

File Name Document Type  
None DOCUMENTS VIEW