Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ARIEL CONDUCTORS TO BE INSTALLED PER 230-24 AND 110-14 - 8' OFF OF ROOF AND USE APPROVED SPLICE INSULATION. 2) GROUNDING ELECTRODE SYSTEM NEEDED AT 2ND STRUCTURE DISCONNECT. 3) DRYWALL SCREWS NOT ALLOWED FOR MOUNTING HARDWARE. 4) PLEASE VERIFY WTR AND GAS BONDS. 5) NM CABLE NOT ALLOWED IN A COMPLETE RACEWAY SYSTEM. 6) #8 THHN AMPACITY ONLY 50 AMPS. #8 NM CABLE AMPACITY ONLY 40 AMPS. 7) PLEASE VERIFY A/C PERMIT FOR NEW SERVICE. |