Permit: T04EL01033
Permit Details
Apply Date:
05/14/2004
Applicant:
WILLIAMSON ENTERPRISES INC , D J
Description:
REPLACE:ELECTRIC SERVICE ENTRANCE
Contractors:
- WILLIAMSON ENTERPRISES INC , D J
Permit Reviews
Permit Number - T04EL01033
Permit Status: Final
Permit Description: REPLACE:ELECTRIC SERVICE ENTRANCE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/14/2004 | ELECTRICAL | 05/14/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04EL01033
Permit Status: Final
Permit Description: REPLACE:ELECTRIC SERVICE ENTRANCE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/14/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T04EL01033
Permit Description: REPLACE:ELECTRIC SERVICE ENTRANCE
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2004 | ELECTRIC - FINAL | RMAJUTA | Approved | 1) ID ALL DISCONNECTS INCLUDING MAIN PERMANENETLY. 2) INSTALL REJECT PINS ALL DISCONNECTS. 3) STRAP ALL FLEX FEEDERS. 4) CHASE OUT PROBLEM IN 400A DISCON OR RUN NEW FEEDERS. 5) CLOSE ALL UNUSED OPENINGS. SINCE EXISTING MAIN DOES NOT HAVE A NUETRAL NEW GROUND MOUNTED IN GUTTER TO ALL GROUNDS . NOTE: EE APPROVED PLAN SHOW USE EXISTING 1200 A MAIN DISCONNECT. CALL FOR FINAL OR FOR APPROVAL PRIOR TO ENERGIZE 400A DISCONNECT. CONTRACTOR PAID FOR INSP. |
| 05/14/2004 | ELECTRIC - CABLE DROP | RMAJUTA | Approved | |
| 05/14/2004 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | |
| 05/14/2004 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | |
| 05/09/2005 | PERMIT FINALED | JKOZUCH | Approved | |
| 05/09/2005 | TEP CLEARANCE - PM | JKOZUCH | Approved | ECO |